1.
|
Theaters
or motion picture theaters. |
|
2.
|
Assembly
rooms or similar places having an assemblage or seating
capacity exceeding 500 persons (See Item 8 below for assembly
rooms having a seating capacity not exceeding 500 persons).
|
|
3.
|
All
health care facilities within the scope of Article 517
of the California Electrical Code. |
|
4.
|
A
new building, or addition, where the computed area exceeds
30,000 square feet (2787 M2), except where the total service
load does not exceed 84 KVA (computed with demand factor,
if allowed). The computed area shall be the sum of the
areas on each floor bounded by the outside surfaces of
the exterior walls and shall include floor areas beneath
building projections which extend more than 6 feet (1829
min). |
|
5.
|
All
electrical installations over 600 volts |
|
6.
|
Installation
in locations classified as hazardous locations, unless
otherwise satisfactory to the department. |
|
7.
|
Proposed
installations, other than Items 1 through 6, where over
600 amperes of load are to be added or where a disconnecting
means rated over 600 amperes is to be installed. |
|
8.
|
Assembly
rooms or similar places having an assemblage capacity
exceeding 200 persons but not exceeding 500 persons.
|
|
9.
|
Installations
of a complicated nature including those which require
an emergency supply system by the provisions of this Code.
Exceptions: |
|
|
i.
|
Plan
check will not be required for the addition of strobe
power supplies and their attached devices connected to
any existing fire control unit (panel). |
|
|
ii.
|
Plan
check will not be required for the installation of special
extinguishing, central station monitoring systems, dialers,
and their attached devices. |
|
|
iii.
|
Plan
check will not be required for the addition of any fire
warning devices connected to a existing programmable fire
warning system. |
|
|
iv.
|
Plan
check will not be required for the installation of any
non-required fire warning system. |
|
10.
|
Installation
of lighting fixtures weighing more than 300 pounds (136
kg). |
|
11.
|
Plans
for an energy analysis are required by Section 98.0403.
1 (e) of the Los Angeles Municipal Code. |
|
12.
|
All
fire alarm installations will require review and approval
for device location by the Los Angeles Fire Department
plan check only (electrical plan check not required for
device location). |
|
13.
|
Exit
sign and egress lighting installations will require review
and approval by the Los Angeles Fire Department. |